Cellular SCADA Communications Troubleshooting

The pervasiveness of Cellular Data Communications has prompted its use in many SCADA, Remote Monitoring, Data Logging, and Video Surveillance applications.

There are instances where the deployed cellular communications is unreliable or has become unreliable. This can be caused by equipment failure,  lack of cellular network coverage, changes in cellular network coverage, or weather related RF path challenges.

When the site or sites are at remote locations that are difficult to access and the application is mission critical it is necessary to follow the proper troubleshooting procedures to ensure that the cellular communications problem is promptly resolved.

The following steps are recommended to repair unreliable cellular communications systems:

  • Cellular Path Study
  • Onsite Cellular Path Test

Path Study

Utilize Cellular Tower Location Apps and RF Path Coverage Software to determine expected cellular signal levels prior to site visit. This is done to understand the terrain and optimal antenna pointing and minimum required antenna heights.

Onsite Cellular Signal Testing

Onsite Cellular Signal testing is performed to verify signal reliability for proposed deployments or to troubleshoot communication problems at existing sites.

The following steps are performed during onsite cellular signal testing.  Note that spare/test equipment (modem, jumper, lightning arresters, antenna) must be be brought for troubleshooting in event of finding a equipment failure.

Measure Received Cellular Signal with a Cell Phone, Cell Phone Signal App, and/or Cellular Signal Analyzer. A Cellular Signal Analyzer is preferred as it has external antennae connection.

Verify Cellular Signal Strength with the Existing Cellular Modem System using its Modem Diagnostics.

Test the VSWR of Antenna, Cable, Lightning Arrester using an Antenna Analyser to insure there is no problem with the antenna system.

Test Antenna Pointing & Height. Use a pipe mast if elevated antenna height is required.

Test System Fade Margin With Variable RF Attenuator after cellular signal is optimized. It is recommended that you have 15 to 20 dB of fade margin.

Use Ping Test on cell modem to determine end to end communications reliability.

Test with Alternate Cellular Modems. Existing cellular modem may be defective or they may not support current 4G / 5G technology.

Test Alternative Antennae systems including YAGI and/or Diversity Antennas.

Test Coverage with Alternative Carriers or Dual Carriers / Dual SIM.

Test Backup Satellite Communications Path (Starlink, BGAN, Iridium) if cellular communication coverage at site is found to be unreliable.

 

 

SCADA Communications Troubleshooting

Overview

SCADA Communications Troubleshooting

Bentek Systems’ extensive experience in SCADA communications technology and equipment, SCADA Hosts, PLC, RTU, EFM, and Data Logger integrations allow us to provide a wide variety of troubleshooting services:

  • Emergency Repairs
  • Temporary Communications Links
  • Troubleshooting of Long Standing Communications Problems
  • System Audit
  • System Re-Design
  • System Consultation

SCADA Communications Problems Addressed

  • Unreliable and Intermittent Communications
  • Excessive Communication Errors
  • Prolonged Communication Outages
  • In-adequate RF Fade Margin
  • Bandwidth Limitations
  • RF Interference
  • Protocol Mismatch
  • Incorrect System Architecture
  • Lightning and Surge Damage Mitigation
  • Cellular Data Overage

Technologies

Bentek Systems has extensive experience in SCADA Communications Technology and Equipment including:

Wireless

MDC SD4

pathstudy_communication_service   Wireless_Tower_Service   satellite dish - communication service  

Wired

  • BEL202, Ethernet, RS232, RS485
  • Surge Protection

Industrial Protocols

  • Modbus RTU/ASCII, Modbus TCP,
  • Ethernet IP, AB-Ethernet, DF1
  • ROC, DNP3
  • Legacy Protocols

Networking

  • Router, Firewalls
  • VPN Networks

RTU/PLC/EFM Devices

  • SCADAPack
  • Fisher ROC, FloBoss
  • Cameron – Scanner 2000, MC-III, 1140
  • Bristol
  • ABB Totalflow
  • Allen Bradley PLC5, Contrologix, CompactLogix
  • Horner PLC/HMI
  • Modicon
  • Prosoft

R2843225-10  ROCEFM

SCADA Hosts

  • ClearSCADA
  • Wonderware
  • Allen Bradley
  • Modicon
  • SCADAvantage
  • Telvent OaSys
  • Kepware
  • Autosol
  • eFCAS
  • PHD, PI Historian’s

SCADA Host Monitoring

Communications Equipment

Wireless Communications

Bentek Systems manufactures and carries a wide-range of radio equipment for SCADA applications. We supply spread spectrum wireless modem, cellular-based high-speed internet modems, licensed radios (330-512MHz), unlicensed radios (900 / 902-928MHz), ethernet radios and satellite systems.

Wireless RTU Modem

Cellular Modems

Radios

Satellite Systems

Antennas and Accessories

 

Blog

Related Products